Copper vs aluminum magnet wire: how to choose for transformers and motors

A practical comparison of conductivity, weight, cost, size and termination so you can pick the right conductor.

Copper vs aluminum magnet wire: how to choose for transformers and motors

Key takeaways

  • Aluminum conducts about 61% as well as copper, so it needs roughly 1.6 times the cross-section for equal resistance.
  • At equal resistance an aluminum winding weighs about half as much as copper and usually costs less.
  • Copper wins where space is tight: small motors, high power density and compact transformers.
  • Aluminum terminations need crimping, welding or aluminum-rated connectors, not ordinary soldering.

The physical numbers

Most of the decision follows from three properties. At 20 °C annealed copper has a resistivity of about 0.01724 Ω·mm²/m (100% IACS). Electrical-grade aluminum is about 0.02826 Ω·mm²/m (61% IACS). Copper has a density of 8.89 g/cm³; aluminum is 2.70 g/cm³.

PropertyCopperAluminum
Resistivity at 20 °C0.01724 Ω·mm²/m0.02826 Ω·mm²/m
Conductivity100% IACSabout 61% IACS
Density8.89 g/cm³2.70 g/cm³
Cross-section for equal resistance1.0×about 1.64×
Weight for equal resistance1.0×about 0.50×
Tensile strength (annealed)about 220 MPaabout 80 MPa

So an aluminum conductor must be about 64% larger in area, about 28% larger in diameter for a round wire, to match copper's resistance. Even at that size it weighs half as much.

Cost

Magnet wire is sold by weight, and aluminum is both lighter and cheaper per kilogram. For an equal-resistance winding the conductor cost is usually well below that of copper, and aluminum prices swing less. That is why distribution transformers, fan motors, ballasts and microwave oven transformers moved to aluminum first.

The saving is not free. A bigger conductor needs a bigger winding window, so core steel, tank and insulation can grow. Always cost the whole unit, not only the wire.

Where copper still wins

  • Space-limited designs. High power density motors, EV traction motors and compact transformers cannot afford a 64% larger conductor.
  • Fine wire. Aluminum's low tensile strength makes very fine sizes break on high-speed winders. CCA or CCAM is a good compromise.
  • Soldered terminations. Copper and CCA solder directly; aluminum does not.
  • Short-circuit strength. Copper's higher strength helps windings survive short-circuit forces.

Where aluminum wins

  • Distribution transformers, especially foil-wound low-voltage coils.
  • Weight-sensitive products such as portable equipment and pole-mounted transformers.
  • Cost-driven appliance motors where the frame has room for the larger winding.

Terminating aluminum

Aluminum forms a hard oxide layer instantly, so ordinary tin-lead soldering will not wet it. Use crimp connectors rated for aluminum, TIG or ultrasonic welding, or cold-pressure welding. Avoid direct contact with copper in humid conditions without a bimetal transition, to prevent galvanic corrosion.

The middle option: CCA

Copper-clad aluminum puts a thin copper skin over an aluminum core. It solders like copper and weighs close to aluminum. It is widely used for voice coils and small motors. See our enameled CCA wire.

Quick decision guide

Choose copper when size, strength or soldering matters most. Choose aluminum when weight and cost dominate and the design has room. If you are converting an existing design, send us the winding data and we will size the equivalent aluminum conductor.

Frequently asked questions

Is aluminum magnet wire cheaper than copper?

Usually yes for an equal-resistance winding, because aluminum is cheaper per kilogram and an equal-resistance winding weighs about half as much. The larger winding can add core and tank cost, so compare complete units.

How much bigger must aluminum wire be to replace copper?

About 1.64 times the cross-sectional area, or about 1.28 times the diameter for round wire.